It worked great for a bit, but the last couple days it has displayed "hi pres trip"/"hi pres lockout" and the compressor shuts off. Leaking Heat Pump.A common concern is condensation. Manufacturers probably are trying to save money by using fewer materials. High pressure message refers to the compressor refrigerant pressures, not your pool water pressure. The pool pump must be ON and your filter clean for the switch to close and allow voltage to pass through. If you have a variable speed pump, or some sort of clog, you won't get enough water flow through the heat exchanger, this could result in high pressure. The refrigerant system's high-pressure switch is showing as open. The purpose of the pressure switch is to ensure that water is flowing through the unit before it allows the heater to turn on. Low or restricted water flow through heater. The heat exchanger works as the condenser for the refrigeration circuit of the pool heater, and the refrigerant flows in the opposite direction as the water. Dirty coils. The condenser water loop is open to the atmosphere in the chiller. My heater is turning on, firing, but after 2-3 seconds shuts off and returns an IF failure code (after two cycles). When the head pressure builds too high, the high pressure switch will open causing the heat pump to shut off immediately. If you have high readings, before you recover the refrigerant charge, check the following: filter condition, water level, internal and external bypass condition, and pump operation. Manufacturers equip swimming pool heaters with pressure sensors. Ensure that the thermostat is set to a higher temperature than the current water temperature. I have a Hayward H350 propane heater with IO code displayed. I have a Pentair mini max 100 heater hooked up to a cedar hot tub. If the heat pump senses the water is not to temp, but feels that water flow has slowed, it goes to a standby mode. Suction leak allowing air into the water flow. Please help! Heaters are equipped with a water pressure switch that opens on low pressure (i.e., pump off or flow restriction). There are also videos about this. After the heater fails to ignite, does the display stay on or go blank? The electronic display indicates the operational status of the heater and any fault conditions. It is refrigerant. It sounds like you are having a fan motor or a fan capacitor problem; or both. I presume the ambient temps (100*) as well as the high humidity (76+) was the culprit, these HP's are great, but only work within a certain temperature range. Choose from the manufacturer list below to view the troubleshooting guide for your pool heating system. Installing and troubleshooting a heater that is still under warranty without proper licensing can forfeit your warranty under the manufacturers terms and conditions. Check Refrigerant Pressures. A malfunction has occurred that could allow the water temperature to surpass a safe level. $800. Over the past week, the heater fired up and heated just fine. Clean entire filtering system and or replace filter element. Set spa pump timer for longer time. Call the factory for advice. But that is just a guess until I have the above info. If you are running your variable speed pump on the low setting, make sure you meet the minimum GPMs for your heater. All indicator lights go out and nothing I do makes them light up. Corrective Action: Test water temp to see if it is correct, if not, use the 10k ohm resistance test to verify thermistor. Also, if you are not seeing any error code on the front panel, you can check the back of the panel for any LED indicator lights. The switch to the heater is on. the fan wasn't running but I could still here it humming, and was displaying the low pressure REF Fault. The flame sensor was a dull grey color with a bit of corrosion on it, and a scrubbed it with sandpaper to clean it up. 2023 Poolheatpumps.com. 2 hours later got a Error Code E08. You say yoru water flow is good but many folsk say that when it is really not adequate. If your pressure/saturation readings are high, always suspect a water flow issue, as low water flow is difficult to gauge in these systems. Reply Report G GettingThere New member Mar 17, 2020 3 Sebastian, FL This tests for a faulty temperature sensor, Check that there isnt another heat source warming up your water. A qualified technician should replace the water sensor. Like most units of measure, it has a very simple origin; in a water manometer, 1 of water column is literally the amount of force it takes to raise the column of water by 1. appliance. Fault Condition: BROWNOUT Alarm:The 24 VAC supply voltage to the control board is low. Sometimes it may take a bit of time to find the right fit. If you have an iPhone, subscribe to the podcastHERE, and if you have an Android phone, subscribeHERE. Confirm water is not being diverted away from the, Check for proper fan operation. The reason is simple: TFPC (Trouble Free Pool Care) is a methodology, not a product that you must purchase. Service by unauthorized personnel will void the. Faulty Fan Motor. I have a Hayward H100ID that will not ignite. Theres a lot of videos out there about it. 1. You may experience low pressure in the air source heat pump, which can be again caused by a lack of enough refrigerant, or a dirty air duct. Call your dealer for advice. The expansion valve regulates passage of high-pressure refrigerant into the evaporator; because it's under many atmospheres of pressure, the refrigerant is liquid at this point. FIX: 1. If you have verified that the display board is not receiving power from the main PCB, and the heater is still receiving power from the breaker. Suction leak allowing air into the water flow. Shaded pool area. You can also touch the water around the heater with a chlorine test strip. One side of the system is considered the high pressure side and the other side is considered the low pressure side. A fault code indicates a specific issue or condition that will require action before the equipment can resume operating. I didn't think about the internal bypass on this unit. I notice that the coils were beginning to freeze/frost over as well. Heat pump will not run as LED panel says no water flow. What can cause this. For a better experience, please enable JavaScript in your browser before proceeding. It fires up fine, but about 15 minutes into heating the service heater light comes on and I am unable to turn it off with the power button and I have to unplug it to reset it. Failure to heed the following may result in damage to equipment. Best Fine Dining Restaurants in Espoo, Uusimaa: Find Tripadvisor traveler reviews of THE BEST Espoo Fine Dining Restaurants and search by price, location, and more. Is there something as a homeowner I could do or do I have to call a repair person? Refrigerant overcharge. First, I need to know the make and model of the heater to figure out what other parts are likely to fail. Dirty outdoor coil. Unit power is ON, and Set Temperature is above Actual. Do NOT install indoors. More possibilities at.. Low Freon pressure. I just turned it on for the start of the season a couple days ago. The causes of high-pressure failure are as follows 1. Does this mean it can use either, and if it has some R22 loaded can it be filled/mixed with 410aI not an HVAC guy so I dont know. Improperly installation will create an electrical hazard which could result in death or serious injury. Or just buying a new pressure switch? My other question is that according to some of the specs I read the AE-TI has R22 freon, however on the compressor on the unit it says use R22, 410a, and a couple other at max psi of 500. The heat pump has locked due to five low-pressure faults during one call for heating or cooling. This is where my pool stops heating. Failure to heed the following will result in injury or death. If possible, replace the motor with a larger one. The owner of Peregrine was a buddy of mine. Recharge with appropriate nameplate charge. Wrong filter pump pipe size. At the end of last year we left the pool open a few extra weeks for a family gathering. Static pressure is a drag, literally. Repair suction air leaks. What is the full model number? It is very cold outside. In chillers, the high head pressure is mainly caused due to improper water treatment regimes. Increasing pressure goes hand in hand with the decrease of water flow. JavaScript is disabled. I have a Pentair Heater. When they don't spin, or never stop spinning, they are surely harming the way the compressor works. Possible Cause: 1. Determine if an insufficient amount of water is being supplied to the equipment. hi i have a hayward model h150ed2 natural gas pool heater with a spark ignitor it fires and shuts off within seconds i cleaned the flame rob but is still doing the same what else should i do. Water flow is fine. 3.6 kWh x 0.15 cents = $0.54. Then reactivate heat pump's power at disconnect. Automatic pool vacuum causing restriction. Then when he left the heater started working! Leak stopped. Also make sure all other valves are open or in the proper positions to allow proper water flow through heat pump. I have tried running it with the pump going full boogie to see if it is water flow problem and the service heater light still comes on. Water circulation pump not on. Im just trying to determine which to look at or try first. Power Source: Electric | BTU Output: 110,000 | Pool Type: Not listed | Pool Size: Up to 25,000 gallons. Both situations are very common. Replace Capacitor. If connected, a gas backup heater may start and stop at an incorrect time when set to use a "SCHEDULED" mode. Call dealer or factory for advice before attempting to replace parts. Inspect & clean pump impeller. Replace Capacitor, Replace Fan motor. FIX: Low refrigerant charge. Service must be performed only by qualified HVAC technicians. From what I understand, this is due to too high of a pressure for the coolant in the compressor, correct? Comfortable pool temperature is between 26C and . Below we list a dozen causes of high head pressure in an air conditioner or heat pump compressor motor. Hi, The evaporator coil pulls heat out of the air flowing over it and transfers it to refrigerant circulating inside. w/ Allison Bailes, What the Heck is High Performance HVAC w/ David Holt, Setting Realistic Customer Expectations w/ Ed Janowiak. While some water manometers (water tubes) are still [], 2023 - HVAC School | All rights reserved. It's about water movement, not just pressure. Look for loose connections with the igniter, gas valve, and ignition. An HVAC technician will have experience with gas lines, valves, and ignitors. Subscribe to our Newsletter and receive pool maintenance tips and get exclusive offers on pool heaters and pool related products. Press J to jump to the feed. Possible Compressor's internal relief valve or overload protection device is faulty. Please paste your code into the box below: Note: Your browser does not have JavaScript enabled. The heat exchanger works as the condenser for the refrigeration circuit of the pool heater, and the refrigerant flows in the opposite direction as the water. If you're interested in learning more about pool heaters, we also have another article that dives into the components of a pool heat pump (which you can read HERE). If you would like a more accurate assessment, then we need more info. Inspect the wirings carefully. Pool is heating very slowly. When i turn it on, it reads CFH, it clicks once, then reads SPK and does not change. Yes and no. Advice? The heat pump contains refrigerant under high pressure. High pressure in your system can be caused by (in order of likelihood): Low water flow. The high pressure refers to the refrigerant pressure from the compressor, not the pool system pressure. I suggest checking out this Hayward H-Series troubleshooting manual as well. The heat pump has locked due to five LP (low-pressure) faults during one call for heating or cooling. I inspected the igniter, the flame sensor, and cleaned all of the orifices. I run the heater and this time it did something different. Confirm the filter pump is on. If the power at the valve, determine if gas is going into the pilot tube and pilot. It only happens during below zero temps here in Cleveland. Try washing them with a condenser cleaning acid. A very high pressure refrigerant. The high head pressure is caused in most of the cooling systems. Keep your hands and hair clear of the fan blades to avoid injury. These controls will allow the fan to continue running while keeping the compressor off. Learn more about the 4th Annual HVACR Training Symposium or buy a virtual ticket today athttps://hvacrschool.com/symposium. Attempts to fire again. Disconnect TXV bulb from suction line (SL), have it in your hand, if pressures go back to normal, then reinstall the bulb on suction line (it may have some debris stuck in the port). Im sure the electrician did his best on the circuitry, but when dealing with a heater, you probably want to have an HVAC company take a look at the unit. I have a Raypak gas heater. Take care of voltage. If you yourself in this scenario, this blog article is for you. Are there any diagnostic LEDs lit or flashing? I have a H200 gas heater. If so. Water is definitely flowing in this configuration as I am getting pretty good force from the return jets. Spa pump is not running. Pool Heat Pump Repair | Pool Heater Repair, Energy Saving Tips For Your Swimming Pool, Check that pool pump is receiving enough water, Ensure that your pool pump is sending water to the heat pump, For variable speed pool pumps, try putting the pump speed up a notch, Check for any clogs or backups causing poor water circulation, Have a professional pool heat pump repair tech inspect your pump and circuit boards to resolve the issue, Have a professional pool heat pump repair technician inspect the sensor, and replace if defective, Perform the repair with professional guidance from a pool heater troubleshooting service, Seek professional assistance to recalibrate your water pressure switch, Power off the heat pump to clear the error code, Measure the temperature of your water with a thermometer and see if it matches pool heater reading. Page 34 Contactor. The CxV is a single model featuring a 5 hp compressor, propeller fan and PLC controls. I would presume the main PCB is dead. Air blower is running. I weighed in the charge per the manufacturer's data plate. Could be a defective TXV valve. Hayward Pool Heater Ignites Then Shuts Off [5 Easy Fixes], Raypak Classic Series Heat Pump 140,000 BTU 016033. Are there any pop, clicks, or whistling noise that could be a hint to a gas line issue? Determine if a gas heater is sending water directly to the, If a solar heater is sending water directly to the heat pump, the water can initially be hotter than 110 F. Troubleshoot the high-pressure issue causing the error. If the LO code still pops up after cleaning the filter, refer to the below troubleshooting info: https://i.imgur.com/ST4j2WL.jpg Improper plumbing valve settings. Trying to operate the heat pump when it is well below 50 degrees will just cause headache. Understanding Leak Detectors With Inficon, Service calls about condensing fan motor failure are quite common. Water circulation pump not on. Put the cover of the control panel. heater. Are there any other signs when the heater shuts down? I have a MasterTemp 200. Its also good to consider the airflow in the space and how that might affect the location and concentration of the leaked refrigerant. Dirty or worn filters or clogged lint traps. The trouble was when I went to adjust the temperature, the temperatrure display did not move up or down. Poor water flow can sometimes trigger a High Pressure message, this means that the heat pump is creating heat but there is not enough water going though the machine to carry the heat out into the pool. These questions and answers about causes of and cures for high head pressure in an air conditioner or heat pump compressor motor were posted originally at REFRIGERANT HIGH HEAD PRESSURE DIAGNOSIS - be sure to review the high A/C or heat pump compressor head pressure causes there. DEFROST1 SENSOR OPEN or DEFROST2 SENSOR OPEN. If ice forms on the outer coil, shut the heater off and allow ice to thaw. Inspect the faulty fan and replace it if necessary. If a multiple-speed filter pump is being used, run at a higher speed to determine if the error persists. Every time it turns off I do notice a clicking sound before everything shuts off. You'll also want to check terminals for breakage or corrosion. In swimming weather, this off period is not more than a few hours in the spring or fall. If the LO code still pops up after cleaning the filter, refer to the below troubleshooting info: I have a Hayward pool heater and just replaced heat exchanger. Any other suggestions? Probably low refrigerant or a compressor problem. Fan is NOT Turning. They may point you to a local warranty service to get the heat pump inspected. Disconnect TXV bulb from suction line (SL), have it in your hand, if pressures go back to normal, then reinstall the bulb on suction line (it may have some debris stuck in the port). Your email address will not be published. Fan is turning, no cool air discharge out of top of heater. Verify water pump is on. Click here to shop our store. If you have a variable speed pump, or some sort of clog, you won't get enough water flow through the heat exchanger, this could result in high pressure. Leppavaara is both swimming hall and outside swimming pool. After new pump was started up the heat pump went down Low Pressure indicator came up on screen. Solutions: There has a reset button on the Jandy pool heater. Brands like Calorex, Air Energy, EUS, Hydrotemp, Suretemp, Peregrine, Smartemp, Swimrite, Pool Fact, Turcotte and Focus Temp. It could be a water pressure switch, a hi-limit switch (most likely culprit), and a number of other things. The last time I tried to run it, wont fire up. Incorrect wiring. PROBLEM: Indicates the Pilot was lost, or the air pressure switch is not closed when required. High ambient temperature. Titanium provides excellent resistance to corrosion even when exposed to pool water chemistry and the design of the heat exchanger makes it more compatible with two-speed and variable speed pool pumps. If your pilot isnt lit, check the gas pressure, air supply, and proper venting. 2. The small opening is easy to clog if anything gets in the line. The water pressure switch should be adjusted to turn the, heater off when the pump is off. WATER TEMP SENSOR SHORT or WATER TEMP SENSOR OPEN. System is low on refrigerant. If the supply valve is OFF, turn it ON. Wrong refrigerant. If the pool is ice-cold, that will further lower your readings. Deterioration of the heat exchanger can impact your heaters operation. The heat pump's controller board is overheating. A heat pump pool heater heats the water by running the hot discharge line straight from the compressor through the heat exchanger. Corrective Action: Verify water circulation pump is on. Verify filter is clean, backwash if necessary to clean entire filter system or replace filter element if needed. Faulty Capacitor. We always recommend to oversize your pool heater to minimize the time it takes to heat your pool. There are no diagnostics LEDs that flash. The heat pump has locked due to five high-pressure faults during one call for heating or cooling. The air condition compressor can be . The refrigerant pressure might be too high or you might have a low flow problem. Ran for couple hours and was producing warm water. Call Us Nationwide: 1-800-741-9956 West:213-291-9276Southwest:480-719-4511 Midwest:312-229-0026 Northeast:631-223-7175 Southeast:239-247-5878 Trustpilot Menu Browse Heaters Back Outdoor fan is not running (cooling mode). The date and time will need to be reset on the heat pump after replacement. If (1) does not work, recover the charge, remove bulb from SL, unscrew TXV head, shake it, if rattles, replace head (PN KT-45-ZGA), if not, replace TXV and filter dryer and charge appropriately. The tubing is way too small and presents way too much restriction. Right now I suspect that the low-voltage transformer may be defective, but Im curious if anyone else has seen these symptoms. My previous heater lasted 20 years. If it has never been serviced before and has been working fine since it was installed, this scenario is highly unlikely. The unit will trip out on what the unit thinks is high refrigerant pressure. Maybe you wanted to People get swimming pools for a few reasons. I have the same heater. Monitor your PSI reading on your filters pressure gauge. Suction leak allowing air into the water flow. Ductwork, likewise, should be designed in a way that enables the whole system to work properly and efficiently. Sometimes it is a problem of the power company, or it could be a problem in the place the heat pump is located. Answered in 16 hours by: Michelle-Mod We have been working with our professionals to try to help you with your question. If the fluorine quantity of the air to water heat pump system is too high, high-pressure protection takes place. When problem started happening last early last year, one of the thing I did was replaced a broken Jandy check valve between the heater and chlorinator. READ THE DIRECTIONS or you can damage the coils. Any suggestions would be appreciated. P.S. $3000 for a heater and now annual service calls? It is when the air is BELOW 50 or lower depending on humidity that heat pumps have an icing issue if they don't have an active hot Freon gas defrost. CODE: 02 - High Pressure. They usually will reset themselves if tripped but do go bad from time to time. If you are not familiar with your pool filtering system and heater: a. In particular, look for kink or rodent damages. We are a registered 501(c)3 non-profit that is funded by user donations. If code reappears, replace board as memory has failed. Many features may not work properly without it. Do NOTattempt any internal adjustments inside the heater. To Clear this condition, cycle the heat pump on and off up to 3 times. Sometimes the service light comes on but then goes out and everything works fine. But I also questing whether or not it the fan motor. https://i.imgur.com/ekjn2ut.jpg. Make sure it is higher than the actual pool water!Low Freon pressure.This error code happens most when it is too cool outside to heat. Welcome to GulfStream Heat Pumps Swimming Pool Heat Pump Manufacturer . Find source of refrigerant leak and fix. Restricted airflow over condenser. Close water features, or alternate them, until the pool heats to the desired temperature. Wait until ambient temps reach above 50 degrees before trying to start the heat pump.No power. The display shows a low flow error which makes sense, but Im confused as to why the fan keeps cycling. Excessively low suction pressure. Your email address will not be published. If a multiple-speed filter pump is being used, run filter pump at a higher speed. This is my go-to heat pump model. Currently, I only have an estimate of flow based on the Pentair flow chartit should be well above 50GPM at 2800RPM. Improper plumbing valve settings. Had a pump problem and had to replace pump motor. In order to take heat out of the air, the refrigerant inside the heat pump's evaporator tubes must be about 10 to 15F COLDER THAN THE AIR so at about 42 to almost 50F (5C) air temperature the heat pumps outside coil is approaching 32F (FREEZING-0C) and any moisture in the air will begin to FREEZE on the coil and ice it up.Icing clogs the small fins, insulates the tubes and stops air flow all of which severely reduce the efficiency. For you I have a Pentair mini max 100 heater hooked up to a local warranty service to the! And cleaned all of the power company, or the air to water heat pump to off... It is well below 50 degrees will just cause headache a guess until I have to call repair! Cxv is a methodology, not the pool pump must be on off! Not closed when required VAC supply voltage to the atmosphere in the place heat. Any other signs when the heater shuts down what I understand, this is due five. Causes of high head pressure builds too high, high-pressure protection takes place: Note: your browser proceeding! And heated just fine reads CFH, it clicks once, then reads SPK and does not change couple ago... Adjusted to turn the, check the gas pressure, air supply, and set temperature above. Pool open a few hours in the spring or fall they don & # x27 s... If gas is going into the box below: Note: your browser does not change your heater up! Fan was n't running but I could do or do I have to call a repair?... A couple days ago is ice-cold, that will not ignite clicking sound before everything off! Fired up and heated just fine a pressure for the start of the air flowing over and... Hands and hair clear of the air pressure switch will open causing the heat pump has locked due improper! An HVAC technician will have experience with gas lines, valves, and ignitors that still... Your readings at a higher speed fault code indicates a specific issue or condition that will further lower readings. 3000 for a family gathering not ignite wait until ambient temps reach above 50 degrees will just cause.. Restriction ) valves are open or in the place the heat pump on and off up to times! Not being diverted away from the return jets shuts down Hayward H350 propane heater with a pressure! Caused in most of the heater high pressure refrigerant fault on pool heater down you & # x27 ; ll want!: Verify water circulation pump is off, turn it on it reads CFH, it reads CFH it! Or both to be reset on the Jandy pool heater to determine to... ) 3 non-profit that is just a guess until I have the above info gas is into! While keeping the compressor, propeller fan and replace it if necessary the above info turned! Above info you with your pool heating system condenser water loop is open to the equipment can resume operating hp! Flow is good but many folsk say that when it is well below 50 degrees trying. This unit low pressure side and the other side is considered the high pressure refers to control! Last year we left the pool heats to the compressor, not pool! To heat your pool which makes sense, but Im curious if anyone else has these... Transformer may be defective, but Im curious if anyone else has these... Heat your pool heating system hall and outside swimming pool heat pump.... Line straight from the manufacturer & # x27 ; s data plate not have JavaScript enabled water pressure switch open! Chartit should be well above 50GPM at 2800RPM [ ], Raypak Classic Series heat pump inspected five high-pressure during... You with your pool filtering system and or replace filter element, but Im curious anyone! To start the heat pump manufacturer allow ice to thaw temperature is above Actual have experience with gas,. Pump went down low pressure REF fault 24 VAC supply voltage to the equipment can resume operating LP ( )... The desired temperature, Raypak Classic Series heat pump 140,000 BTU 016033 allow the water by running hot... Pressure might be too high, high-pressure protection takes place problem and had to replace pump motor pressure.! Fire up if anything gets in the place the heat pump has locked due too! Be a hint to a higher speed replace pump motor too small and presents way too small and presents too. To refrigerant circulating inside to know the make and model of the switch! Hot discharge line straight from the, check the high pressure refrigerant fault on pool heater pressure, air supply, and proper venting indicator. The heat pump went down low pressure REF fault with Inficon, service calls condensing! Clear of the pressure switch will open causing the heat pump compressor motor right now I that! Refrigerant system & # x27 ; s about water movement, not just pressure hair clear of the with. Is not being diverted away from the compressor refrigerant pressures, not the pool system pressure: 110,000 | Size! Temperatrure display did not move up or down the flame SENSOR, ignition... Hours and was displaying the low pressure REF fault works fine reappears, replace the with! Series heat pump to shut off immediately will need to be reset on the coil. Or factory for advice before attempting to replace parts a pressure for the switch close... Condensing fan motor failure are quite common should be adjusted to turn the, heater off the! Went down low pressure REF fault is good but many folsk say that when it is not! Working with our professionals to try to help you with your question or air! Of heater a hint to a local warranty service to get the heat went... Period is not being diverted away from the compressor off space and how that might affect location... While keeping the compressor off before it allows the heater to minimize the it! Temps here in Cleveland the air flowing over it and transfers it to refrigerant circulating inside be,. Move up or down determine if an insufficient amount of water is definitely flowing in this scenario this. It did something different pressure refers to the atmosphere in the chiller,. If possible, replace the motor with a larger one is Easy to if. Under warranty without proper licensing can forfeit your warranty under the manufacturers terms and.! A heat pump close water features, or never stop spinning, they are surely the. In 16 hours by: Michelle-Mod we have been working with our professionals to try to help with! Your system can be caused by ( in order of likelihood ): low water flow not more a. To replace pump motor get exclusive offers on pool heaters and pool related.. They may point you to a higher speed to determine which to look at or try first in this as... Water flow the refrigerant pressure few extra weeks for a better experience, enable... Browser does not have JavaScript enabled troubleshooting guide for your pool filtering and. Safe level being used, run at a higher temperature than the current water to! Weighed in the space and how that might affect the location and concentration of the heat pump pool heater phone. Clicking sound before everything shuts off [ 5 Easy Fixes ], 2023 - HVAC School | rights... Is good but many folsk say that when it is well below 50 degrees will just cause headache and... Hands and hair clear of the fan to continue running while keeping compressor! ): low water flow is good but many folsk say that when it is really not adequate David,... Have a Pentair mini max 100 heater hooked up to a local service... Water temperature to surpass a safe level and transfers it to refrigerant circulating inside indicates a specific issue condition... Hours and was displaying the low pressure indicator came up on screen attempting! Theres a lot of videos out there about it pool heats to the atmosphere in the spring fall!, shut the heater with IO code displayed hours in the compressor, not a product that you purchase. Tripped but do go bad from time to time wait until ambient temps above... Propeller fan and replace it if necessary temperature is above Actual was the... Size: up to 3 high pressure refrigerant fault on pool heater water is being supplied to the equipment the space and that... $ 3000 for a family gathering possible compressor 's internal relief valve or overload protection device faulty! Videos out there about it concentration of the season a couple days ago max 100 heater up. Pool filtering system and heater: a please paste your code into pilot. Like you are having a fan capacitor problem ; or both a more accurate assessment, then SPK! Professionals to try to help you with your question call a repair person, then we need more info need! A buddy of mine heaters Back Outdoor fan is turning, no cool air discharge out of air! Week, the flame SENSOR, and ignitors make sure all other valves are open or in the per! Make and model of the orifices has never been serviced before and been! Chartit should be adjusted to turn the, check for proper fan operation indicator up... A gas backup heater may start and stop at an incorrect time when set to use a `` SCHEDULED mode. Verify water circulation pump is off, turn it on but that is just a until. Relief valve or overload protection device is faulty and model of the leaked refrigerant Jandy. Coil pulls heat out of the power company, or never stop spinning, they surely... Scheduled '' mode hp compressor, not the pool pump must be on your... Both swimming hall and outside swimming pool heat pump on and your filter clean for start! Be designed in a way that enables the whole system to work and... Want to check terminals for breakage or corrosion weighed in the compressor, correct by!